Cable Size Estimator

Minimum standard cable cross-section to keep voltage drop within your limit.

Inputs

V
A
m
%

Results

Recommended size
10 mm²
Minimum calculated area
6.38 mm²
Voltage drop at that size
1.91 %

⚠ Also check current-carrying capacity, installation method and protective device rating per your local wiring code.

Formula

A min = k × I × L × ρ ÷ (V × max drop %)

k = 2 (single/DC) or √3 (three-phase); pick next standard size

Assumptions & limits

  • Voltage-drop sizing only — an estimator, not a code-compliant design.
  • Conductor resistivity at 20 °C.

Worked example

2 × 32 × 40 × 0.0172 ÷ 6.9 = 6.38 mm² → 10 mm².