quickcalq.com

Voltage Drop Calculator

Voltage drop and end voltage for copper or aluminium cables in DC, single- and three-phase circuits.

Inputs

V
A
m
mm²

Results

Voltage drop
3.59 %
Voltage drop
8.26 V
Voltage at load
221.7 V

Formula

Single-phase / DC: Vd = 2 × I × L × ρ ÷ A

Three-phase: Vd = √3 × I × L × ρ ÷ A

ρ Cu = 0.0172, Al = 0.0282 Ω·mm²/m

Assumptions & limits

  • Resistance at 20 °C; conductors at operating temperature drop ~20% more.
  • Reactance ignored (fine for small cables).

Worked example

2 × 20 × 30 × 0.0172 ÷ 2.5 = 8.26 V = 3.59%.